KB-126757: SEW MOVITOOLS

SEW MOVITOOLS

octoplant supports the management of MOVITOOLS® MotionStudio projects and enables the cyclical monitoring of units that were projected in this development environment.

SEW_MOVITOOLS_Integration_Diagram.png

Image: Integration SEW MOVITOOLS

System compatibility

MOVITOOLS® MotionStudio 5.6.0: SP1 5.72 6.0.0.1 6.10 6.20 6.30 6.40
versiondog 3.3.3 ✓* ✓* ✓
versiondog 8.1.5 ✓* ✓* ✓ ✓ ✓** ✓** ✓**

|

  • Upload only

** Upload requires running the service(s) in application mode.

Example for the server:

```"C:Program Files (x86)vdogServerVDogMasterService.exe" /at:s /rd:D:vdServerArchive /app /visibl e```

Example for the agents:

```"C:Program Files (x86)vdogAgentsVDogCompareAgent.exe" /at:s /rd:D:vdAgentArchive /app /visibl e```
```"C:Program Files (x86)vdogAgentsVDogUploadAgent.exe" /at:s /rd:D:vdAgentArchive /app /visibl e```

Other requirements

A licensed version of MOVITOOLS® MotionStudio must be installed on the octoplant server or the computer from which the upload is performed (server or agent).


Devices supported by SEW-EURODRIVE:

MOVIDRIVE (B) MOVITRAC (B) MOVIAXIS MOVIMOT (D) MOVIFIT (Technology, Classic) MOVIGEAR (DSC, DAC, DBC, SNI) DRC (DSC, DAC, DBC, SNI) MOVIPRO (SK, SDC, ADC) MOVI-PLC (basic, advanced) CCU (advanced, power)

Key features and functions

  • Detail comparator for configuration and firmware (version detailed comparison)

  • Automatic detection of program changes (version and backup detailed comparison)

  • SmartCompare for MOVITOOLS® MotionStudio projects (version detailed comparison)
  • Clear presentation of complete change history
  • Component type for MOVITOOLS® MotionStudio projects
  • Integrated MOVITOOLS® MotionStudio project tree
  • Open the editor directly from
  • Upload configuration for MOVITOOLS® MotionStudio

Notes about the comparison

  • Device data is compared with the VarData-Interpreter application from MOVITOOLS® MotionStudio.
  • Devices that are solely connected through Networks will not be taken into consideration when comparing the parameters.

  • In addition to the parameters that are excluded by the VarData-Interpreter, octoplant also excludes the following parameters:

8455.0: PA1 setpoin 9081.0: Debug address
8456.0: PA2 setpoin 9082.0: Debug address
8457.0: PA3 setpoin 9083.0: Debug address
8458.0: PE1 actual valu 9084.0: Debug address
8459.0: PE2 actual valu 9085.0: Debug Index 1 and
8460.0: PE3 actual valu 9086.0: Debug Index 3 and
8705.0: Sampling tim 9087.0: Debug Index 5 and
8706.0: Scope follow-up cycle 9088.0: Debug Index 7 and
8707.0: Scope Trigger Sourc 9089.0: Trigger behaviou
8708.0: Scope rising edg 9090.0: Trigger selectio
8717.0: Scope Debug Address 9091.0: Trigger sourc
8718.0: Scope Debug Address 9092.0: Trigger mod
8719.0: Scope Debug Address 9093.0: Analogue trigger leve
8720.0: Scope Debug Address 9094.0: Analogue trigger hysteresi
9095.0: Analogue trigger mas