KB-126990: CODESYS

CODESYS

octoplant supports the management of CODESYS projects and enables the cyclic monitoring of devices that have been projected with this development environment.

Image: Integration CODESYS

System requirements

CODESYS V 2.1 V 2.3 V 3.5 SP 9 V 3.5 SP 10 -SP 15 V 3.5 SP 16 -SP 18
versiondog 2.5 ✓ ✓
versiondog 4.5 ✓ ✓ ✓
versiondog 8.0 ✓ ✓ ✓ ✓
versiondog 9.7 ✓ ✓ ✓ ✓ ✓

|

Other system requirements

  • The upload is carried out using the CODESYS PLC Handler.
  • The comparison requires an installed CODESYS Editor with the compatible version.

octoplant automatically searches through the listed software for the correct editor in the following order (*only CODESYS V2X):

  • CODESYS
  • SoMachine (CODESYS V3)
  • CPS21 (Bosch)*
  • TwinCat (Beckhoff)** TwinCAT V3 contains its own editor.
  • MOVITOOLS® MotionStudio (SEW-EURODRIVE)*
  • ELAU (Schneider Electric)
  • Indralogic (Bosch Rexroth)*
  • EATON

Limitations

CODESYS V2.X:

  • For technical reasons, Project information and Block properties are not recognized during comparison.

CODESYS V3.X: An upload is not currently possible. – Visualisation and user management are not supported.

Key features and functions

  • Backup of all CODESYS-supported controllers that are accessible via CODESYS gateway server

  • Automatic change recognition between the program on the device and the current version on the server (backup detailed comparison, version and backup detailed comparison)

  • Clear presentation of complete change history
  • Custom component type for CODESYS projects
  • SmartCompare for CODESYS projects (version comparison)
  • Integrated CODESYS project tree
  • Open the editor directly from
  • Individual upload configuration for CODESYS

Last update: September 15, 2023