Restrictions with regard to carrying out a station upload
- Carrying out a station upload is normally possible for all S7-1500 PLCs, except for software controllers. For software controllers (that is to say, 1505S/HW 1515SP and 1507S / 1508S and their F variants) a station upload is not technically possible.
- For 1500 series F controllers, the Enable consistent loading of F-CPU checkbox must checked in the F program beforehand, so that an upload is possible.
- The dependencies for the project languages must be configured correctly before a station upload takes place (see Requirements for creating an upload job and carrying out version and backup comparisons).
-
When using F-HMI panels, F-Drives, SITOP devices, PACs*, a station upload can block the S7-1500 controllers.
-
You can only upload a SIMATIC PLC with a connected SENTRON device in SIMATIC STEP 7 (TIA Portal) V15.1 and V16 if you have placed the SENTRON device using GSD or GSDML. In this use case, do not create a version of the SENTRON project that was integrated in the TIA Portal. For more details, go to the Siemens website.
Note
For more information, see Requirements for creating an upload job and carrying out version and backup comparisons.
Last update: September 15, 2023