Configuring the access path
The available access paths and settings for each access path are displayed below.
When using the H1 protocol:
-
For connections via H1 protcol, you will need the INAT H1 driver. This is provided with versiondog and can be used up to Windows Server 2008. If the versiondog Server is installed on a computer that is not able to able operate the driver, you will need to either:
- install another H1 driver that is compitable with the server operating system
- or the upload will need to be carried out using an agent on a computer with the driver installed.
-
When using a H1 protocol, we recommend that you deactivate the_QoS Packetplaner_on the network card in question.
- When using a H1 protocol, you need to ensure that H1 protocols from other producers have been deactivated on the network card in question.
Warning
The versiondog server cannot communicate with an access path via a main device. Please check if your
type of device is routing compatable. If the CP device is not suitable for routing, you will not be able to communicate with the MPI/Profbius subnet via the main device.
When using a IBH-Link:
- An additional driver is required for the converter (IBH link). This is not supplied with versiondog, but must be obtained and installed separately via the website https://www.ibhsoftec.com/DL-IBHNet.
- Communication is not carried out directly via the VDogUpload.exe application but via the IBH_NETPCOM.exe. This is accessible via port 1099 by default. Port 1099 must be enabled in the firewall.Image: IBH-NETPCOM.exe propertiesAlternatively, another port can also be configured via the configuration software of the driver in the IBHLink Settings dialog.
Image: Dialog IBH-Link settings
When accessing the S7 controller using the IBH-Link, an error occurs. How to proceed?
Image: Eventlog module, no driver installed via IBH-Link
If this error is issued, no driver for IBH-Link has been installed. This driver is not supplied with versiondog, but must instead be obtained and installed separately via the website https://www.ibhsoftec.com/DL-IBHNet.
Image: Module Eventlog, connection via port not possible
If this error is issued, the connection via the port is not possible. Unlock the port in the firewall or configure another port for the IBH-Link.