KB-133333: Configuring the access path

Configuring the access path

The following table shows the available access paths together with their possible settings. In the section Access path details, select the access path that applies to your specific application.

Access via the INAT H1 ISO protocol

  • Select the access path [0201] PC->[H1]->PLC.
  • Activate the option Backplane bus if your S5 devices communicate via the backplane and not via the AG cable S5-CP/AG.
  • Enter the PLC’s H1 address.
  • Enter the CP password.

Access via the INAT H1 ISO protocol and then a KOR-MUX/TELE-Switch interface switch

  • Select the access path [0202] PC->[H1]->KOR/MUX->PLC.
  • Enter the H1 address of the interface switch.
  • Enter the CP password.
  • Enter the interface number for KOR/MUX.

Access via the INAT ISO protocol and then an Echolink serial Ethernet converter

  • Select the access path [0203] PC->[H1]->Echolink->PLC.
  • Enter the H1 address of the Echolink device.
  • Enter the Echolink port to which the PLC is connected.

Note

The Echolink device can reach up to 5 CPUs via the AS511 protocol.

Access via the INAT H1 ISO protocol, an Echolink serial Ethernet converter and then a KOR-MUX/TELE-Switch interface switch

  • Select the access path [0204] PC->[H1]->Echolink->KOR/MUX->PLC.
  • Enter the H1 address of the Echolink device.
  • Enter the interface number for KOR/MUX.
  • Enter the Echolink port to which the interface switch is connected.

Access via the INAT H1 ISO protocol, an Echochange Ethernet converter and then H1/TCP/IP

  • Select the access path [0205] PC->[H1]->Echochange->[H1][TCP/IP]->PLC.
  • Activate the option Backplane bus if your S5 devices communicate via the backplane and not via the AG cable S5-CP/AG.
  • Enter the H1 address of the Echochange gateway.
  • Enter the CP password.
  • Enter the own TSAP.
  • Enter the remote TSAP.

Access via the INAT H1 ISO protocol, Echochange Ethernet converter and then a KOR-MUX/TELE-Switch interface switch

  • Select the access path [0206] PC->[H1]->Echochange->[H1][TCP/IP]->KOR/MUX->PLC.
  • Enter the H1 address of the Echochange gateway.
  • Enter the CP password.
  • Enter the interface number for KOR/MUX.
  • Enter the own TSAP.
  • Enter the remote TSAP.

Access via the AS511 protocol

  • Select the access path [0281] PC->[AS511]->PLC.

Access via TCP/IP

  • Select the access path [0241] PC->[TCP/IP]->PLC.
  • Activate the option Backplane bus if your S5 devices communicate via the backplane and not via the AG cable S5-CP/AG.
  • For the Device, enter the host name/IP address of the PLC.

Access via TCP/IP and then a KOR-MUX/TELE-Switch interface switch

  • Select the access path [0242] PC->[TCP/IP]->KOR/MUX->PLC.
  • For the Device, enter the host name/IP address of the interface switch.
  • Enter the interface number for KOR/MUX.

Access via TCP/IP and then an Echolink serial Ethernet converter

  • Select the access path [0243] PC->[TCP/IP]->Echolink->PLC.
  • For the Device, enter the host name/IP address of the Echolink device.
  • Enter the Echolink port to which the PLC is connected.

Note

The Echolink device can reach up to 5 CPUs via the AS511 protocol.

Access via TCP/IP, an Echolink serial Ethernet converter and then a KOR-MUX/TELE-Switch interface switch

  • Select the access path [0244] PC->[TCP/IP]->Echolink->KOR/MUX->PLC.
  • For the Device, enter the host name/IP address of the Echolink device.
  • Enter the interface number for KOR/MUX.
  • Enter the Echolink port to which the interface switch is connected.

Access via TCP/IP, an Echochange Ethernet converter and then H1/TCP/IP

  • Select the access path [0245] PC->[TCP/IP]->Echochange->[H1][TCP/IP]->PLC.
  • For the Device, enter the host name/IP address of the Echochange gateway.
  • Enter the TCP/IP-Port of the Echochange gateway.
  • Enter the CP password.

Access via TCP/IP, an Echochange Ethernet converter and then a KOR-MUX/TELE-Switch interface switch

  • Select the access path [0246] PC->[TCP/IP]->Echochange->[H1][TCP/IP]->KOR/MUX->PLC.
  • For the Device, enter the host name/IP address of the Echochange gateway.
  • Enter the TCP/IP-Port of the Echochange gateway.
  • Enter the CP password.
  • Enter the interface number for KOR/MUX.

Access via the INAT H1 ISO protocol, a communication processor (CP) and then the L2 protocol

  • Select the access path [0207] PC->[H1]->CP-L2->[L2]-CP-L2->PLC.
  • Enter the H1 address of the communication processor.
  • Enter the L2 bus address of the PLC.

Access via the INAT H1 ISO protocol, a communication processor (CP) a KOR-MUX/TELE-Switch interface switch and then the L2 protocol

  • Select the access path [0208] PC->[H1]->CP-H1->KOR/MUX->CP-L2->[L2]->CP-L2->PLC.
  • Enter the H1 address of the communication processor.
  • Enter the CP password.
  • Enter the interface number for KOR/MUX.
  • Enter the L2 bus address of the PLC.

Access via the INAT H1 ISO protocol, an Echolink serial Ethernet converter, a communication processor and then the L2 protocol

  • Select the access path [0209] PC->[H1]->Echolink->CP-L2->[L2]->PLC.
  • Enter the H1 address of the Echolink device.
  • Enter the Echolink port to which the communication processor is connected.
  • Enter the L2 bus address of the PLC.

Access via the INAT H1 ISO protocol, an Echolink serial Ethernet converter, a KOR-MUX/TELE-Switch interface switch, a communication processor (CP) and then the L2 protocol

  • Select the access path [0210] PC->[H1]->Echolink->KOR/MUX->CP-L2->[L2]->PLC.
  • Enter the H1 address of the Echolink device.
  • Enter the interface number for KOR/MUX.
  • Enter the Echolink port to which the interface switch is connected.
  • Enter the L2 bus address of the PLC.

Access via the INAT H1 ISO protocol, an Echochange Ethernet converter, a communication processor (CP) and then the L2 protocol

  • Select the access path [0211] PC->[H1]->Echochange->[H1][TCP/IP]->CP-L2->[L2]->CP-L2->PLC.
  • Enter the H1 address of the Echochange gateway.
  • Enter the CP password.
  • Enter the local TSAP.
  • Enter the remote TSAP.
  • Enter the L2 bus address of the PLC.

Access via the INAT H1 ISO protocol, an Ecochange Ethernet converter, a KOR-MUX/TELE-Switch interface switch, a communication processor (CP) and then the L2 protocol

  • Select the access path [0212] PC->[H1]->Echochange->[H1][TCP/IP]->KOR/MUX->CP-L2->[L2]->CP-L2->PLC.
  • Enter the H1 address of the Echochange gateway.
  • Enter the CP password.
  • Enter the interface number for KOR/MUX.
  • Enter the own TSAP.
  • Enter the remote TSAP
  • Enter the L2 bus address of the PLC.

Access via TCP/IP, a communication processor (CP) and then the L2 protocol

  • Select the access path [0247] PC->[TCP/IP]->CP-L2->[L2]->PLC.
  • For the Device, enter the host name/IP address of the communication processor.
  • Enter the L2 bus address of the PLC.

Access via TCP/IP, a KOR-MUX/Tele-Switch interface switch, a communication processor (CP) and then the L2 protocol

  • Select the access path [0248] PC->[TCP/IP]->KOR/MUX->CP-L2->[L2]->CP-L2->PLC.
  • For the Device, enter the host name/IP address of the interface switch.
  • Enter the interface number for KOR/MUX.
  • Enter the L2 bus address of the PLC.

Access via TCP/IP, an Echolink serial Ethernet converter, a communication processor (CP) and then the L2 protocol

  • Select the access path [0249] PC->[TCP/IP]->Echolink->CP-L2->[L2]->CP-L2->PLC.
  • For the Device, enter the host name/IP address of the Echolink device.
  • Enter the Echolink port to which the communication processor is connected.
  • Enter the L2 bus address of the PLC.

Access via TCP/IP, an Echolink serial Ethernet converter, a KOR-MUX/TELE-Switch interface switch, a communication processor (CP) and then the L2 protocol

  • Select the access path [0250] PC->[TCP/IP]->Echolink->KOR/MUX->[L2]->CP-L2->PLC.
  • For the Device, enter the host name/IP address of the Echolink device.
  • Enter the interface number for KOR/MUX.
  • Enter the Echolink port to which the interface switch is connected.
  • Enter the L2 bus address of the PLC.

Access via TCP/IP, an Echochange Ethernet converter, a communication processor (CP) and then the L2 protocol

  • Select the access path [0251] PC->[TCP/IP]->Echochange->[H1][TCP/IP]->CP-L2->[L2]->CP-L2->PLC.
  • For the Device, enter the host name/IP address of the Echochange gateway.
  • Enter the TCP/IP-Port of the Echochange gateway.
  • Enter the CP password.
  • Enter the L2 bus address of the PLC.

Access via TCP/IP, an Echochange Ethernet converter, a KOR-MUX/TELE-Switch interface switch, a communication processor (CP) and then the L2 protocol

  • Select the access path [0252] PC->[TCP/IP]->Echochange->[H1][TCP/IP]->KOR/MUX->CP-L2->[L2]->CP-L2->PLC.
  • For the Device, enter the host name/IP address of the Echochange gateway.
  • Enter the TCP/IP-Port of the Echochange gateway.
  • Enter the CP password.
  • Enter the interface number for KOR/MUX.
  • Enter the L2 bus address of the PLC.

Access via TCP/IP and an S5 LAN++ module

  • Select the access path [0291] PC->[TCP/IP]->S5-LAN++->PLC.
  • For the Device, enter the host name/IP address of the S5 LAN++ module.

Note

Please note:

  • For connections via the H1 protocol, the INAT H1 driver is required. The driver is included with versiondog and can be used up to and including Windows Server 2008. If the versiondog server is installed on a computer on which the driver does not work, then either
    • a different H1 driver must be installed that works on the server’s operating system, or
    • the upload must be carried out using an agent via a computer on which the driver is installed
  • When using the H1 protocol, it is advisable to deactivate the QoS Packet Scheduler on the appropriate network card
  • When using the H1 protocol, H1 protocols from other manufacturers must be deactivated on the appropriate network card
  • Please note that the TSAPs must have a length of at least 2 bytes and at most 16 bytes. In order to establish the connection, the TSAPs must match up when viewed crosswise! This means the local TSAP of one system must be the same as the remote TSAP of the other system.
  • A valid installation of the program PLC-VCOM.EXE by Process-Informatik, version 2.79 or newer, is required.
    • The program must be removed from all autostart processes (startup, Task Scheduler etc.).

Last update: September 15, 2023

Related Articles

IMPRINT | PRIVACY POLICY | COOKIE POLICY

Privacy Preference Center